Indoor Unit Control Pcb Abnormality - Daikin VRV RXYQ72-384XAYCA Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code
3.4

Indoor Unit Control PCB Abnormality

Applicable
All indoor unit models
Models
A1
Error Code
Method of Error
Check data from EEPROM.
Detection
Error Decision
When data could not be correctly received from the EEPROM
Conditions
EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power supply
is turned OFF.
Supposed
 Defective indoor unit control PCB
Causes
 External factor (Noise, etc.)
Troubleshooting
231
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn the power supply OFF,
then the power ON again.
Does the
system return to
normal?
NO
YES
SiUS342004EB
The indoor unit control PCB
(A1P) is normal.
External factor other than
error (for example, noise
etc.).
Replace the indoor unit
control PCB (A1P).