Daikin VRV RXYQ72-384XAYCA Service Manual page 184

Heat pump 60 hz
Table of Contents

Advertisement

Field Settings for Outdoor Unit
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
1
COOL/HEAT
Several systems as 1 zone change
selection
over COOL/HEAT:
 INDIVIDUAL: VRV indoor unit or
A-B-C input set mode.
0
 MASTER: System is the
COOL/HEAT master unit.
 SLAVE: System is not a
COOL/HEAT master.
COOL/HEAT
Used to make address setting for
1
unified address
cool/heat unified operation.
Low noise/
Used to make address setting for
2
demand address
low noise/ demand operation.
Indoor fan forced
Used to force the fan of indoor unit
5
H
to H tap.
Forced
Used to force all indoor units to
6
thermostat
operate forced thermostat ON.
Te setting
Used to make setting of targeted
evaporating temperature for
cooling operation.
8
Tc setting
Used to make setting of targeted
condensing temperature for
9
heating operation.
External low
Used to receive external low noise
12
noise setting/
or demand signal.
demand setting
AIRNET address Used to set address of AIRNET
13
Heat pump
Used for heat pump lockout
16
lockout 1
High ESP setting
Fan high static pressure setting
18
FAN
Additional
Used to perform additional
20
refrigerant
refrigerant charging operation
charge
(compressor operation).
Refrigerant
Used to set the system to
21
recovery and
refrigerant recovery mode (without
vacuuming
compressor run).
Automatic night-
Automatic night-time low noise
time low noise
operation.
22
operation
Time for the operation is subject to
the start and end time settings.
External low
Low noise level when the external
25
noise level
low noise signal is input at option
DTA104A61/62.
Automatic night-
Time to start automatic "night-time
time low noise
low noise" operation. ("Night-time
26
operation start
low noise" level setting should also
be made.)
Automatic night-
Time to stop automatic "night-time
time low noise
low noise" operation. ("Night-time
27
operation stop
low noise" level setting should also
be made.)
177
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Individual
Unified Master
Unified slave
0
0
Address:
0
1
0 ~
31
Address:
0
2
0 ~
31
Normal operation
0
5
Indoor fan H
Normal operation
0
6
Forced thermostat ON
Auto
6°C (42.8°F)
7°C (44.6°F)
0
8
8°C(46.4°F)
9°C(48.2°F)
10°C (50.0°F)
11°C (51.8°F)
Auto
41°C (105.8°F)
0
9
43°C (109.4°F)
46°C (114.8°F)
Input LNO/DE
1
2
NO
YES
Address:
0 ~
1
3
63
OFF
1
6
ON
OFF
1
8
ON
Refrigerant charging
OFF
2
0
ON
Refrigerant recovery
2
1
OFF
ON
OFF
Level 1
2
2
Level 2
Level 3
Level 1
2
5
Level 2
Level 3
About 8:00 PM
About 10:00 PM
2
6
About 12:00 AM
About 6:00 AM
About 7:00 AM
2
7
About 8:00 AM
Part 5 Field Settings and Test Operation
SiUS342004EB
7 segment
display
Range
SEG
SEG
SEG
1
2
3
0
1
2
0
3
1
0
3
1
0
1
0
1
0
2
3
4
5
6
7
0
1
3
6
0
1
0
6
3
0
1
0
1
0
1
0
1
0
1
2
3
1
2
3
1
2
3
1
2
3