Part 5 Field Settings and Test Operation
shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are installed
match the total number of indoor units which are recognized by the system. In case
there is a mismatch, it is advised to check the communication wiring path between
outdoor and indoor units (F1/F2 communication line).
shows the total number of connected outdoor units.
It can be convenient to check if the total number of outdoor units which are installed
matches the total number of outdoor units which are recognized by the system. In
case there is a mismatch, It is advised to check the communication wiring path
between outdoor and outdoor units.
shows the latest error code.
shows the 2nd last error code.
shows the 3rd last error code.
When the latest error codes were reset by accident on an indoor unit user interface,
they can be checked again through this monitoring settings.
shows the current cooling comfort setting.
shows the current heating comfort setting.
shows the current high pressure sensor value (psi).
shows the current low pressure sensor value (psi).
shows the current compressor speed (Hz).
shows the current EEV (heat exchanger upper) opening (pulse divided by 10).
shows the current EEV (heat exchanger lower) opening (pulse divided by 10).
shows the current discharge thermistor value (°F).
shows the current compressor body thermistor value (°F).
shows the current outdoor air thermistor value (°F).
shows the current compressor suction thermistor value (°F).
shows the current subcooling gas thermistor value (°F).
shows the current heat exchanger gas (upper) thermistor value (°F).
shows the current heat exchanger gas (lower) thermistor value (°F).
shows the current deicer thermistor value (°F).
shows the compressor run time (hour divided by 100).
Field Settings for Outdoor Unit