SiUS342004EB
Image of operation in the case of A
Power consumption
Rated
70%
40%
Forced thermostat OFF
(Fan operation)
Image of operation in the case of B
Power consumption
Rated
70%
The power consumption set with Demand 1 level setting.
Image of operation in the case of A and B
Power consumption
Rated
70%
40%
Forced thermostat OFF
(Fan operation)
Part 5 Field Settings and Test Operation
Demand level 1
instructing
Power consumption set by
Demand 1 level setting.
The power consumption set with
Demand 1 level setting.
Demand level 2
Demand level 3
instructing
instructing
Demand level
Demand level
2 instructing
3 instructing
Field Settings for Outdoor Unit
The power
consumption
during the
demand level 1
instructing can be
set with the
Demand 1 level
setting.
(70% of rated
power
consumption has
been set at
factory.)
When the
Normal demand
setting is set to
ON (OFF has
been set at
factory.), the
power
consumption can
be set with the
Demand 1 level
setting. (70% of
rated power
consumption has
been set at
factory.)
The power
consumption can
be set with the
Demand 1 level
setting. (70% of
rated power
consumption has
been set at
factory.)
During continuous
demand operation, when
the external demand
instruction is received
repeatedly, the instruction
with higher demand level
has the precedence.