Capacity Range

4. Capacity Range
4.1

Connection Ratio

outdoor units
outdoor units
outdoor units
Notes:
4.2

Outdoor Unit Combinations

Capacity range (ton)
RXYQ
Max. number of
connectable indoor units
Total capacity index of
indoor units to be
connected 1
Capacity range (ton)
RXYQ
Max. number of
connectable indoor units
Total capacity index of
indoor units to be
connected 1
Notes:
1. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units and 130% for triple outdoor units.
17
Total capacity index of the indoor units
Connection ratio =
Capacity index of the outdoor units
Min.
Type
combination
ratio
Single
Double
50% 1
Triple
RXYQ72XA, RXYQ72XB: 70%
1.
If the operational capacity of indoor units is more than 130%, low airflow
2.
operation is enforced in all the indoor units. This limitation can be deactivated
through field setting. Refer to page 188 for detail.
3.
When outdoor-air processing units (FXMQ-MF) and standard indoor units are
connected, the total connection capacity of the outdoor-air processing units
(FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And
the connection ratio must not exceed 100%.
4.
Regarding the combinations related to the low-temperature hydrobox (HXY-TA),
refer to the service manual SiUS392016EA. Low-temperature hydrobox can only
be connected to single module outdoor units.
6
8
72XA
96XA
72XB
96XB
12
16
51-93
48-124
(144)
(192)
20
22
240XA
264XA
240XB
264XB
41
45
120-312
132-343
(384)
(422)
Max. combination ratio
Types of connected indoor units
When using at
When using only
least one
FXFQ12-54AA,
FXFQ07/09AA,
FXDQ-M,
FXFQ07/09T,
FXSQ07-54TA,
FXZQ05TA,
FXSQ07-54TB,
FXZQ05TB,
FXMQ-PB,
FXSQ05TA,
FXAQ-P
FXSQ05TB
180% 2
200% 2
160% 2
130% 2
10
12
120XA
144XA
120XB
144XB
20
25
60-156
72-187
(240)
(288)
24
26
288XA
312XA
288XB
312XB
49
54
144-374
156-405
(460)
(499)
SiUS342004EB
Type of connected
air treatment equipment
FXMQ-MF
When using
When
other indoor
FXMQ-MF
unit models
is only
connected
200% 2
160% 2
100%
130%
14
16
168XA
192XA
168XB
192XB
29
33
84-218
96-249
(336)
(307)
28
30
336XA
360XA
336XB
360XB
58
62
168-436
180-468
(537)
(468)
Part 1 General Information
When
FXMQ-MF
and indoor
units are
connected
100% 3
18
216XA
216XB
37
108-280
(345)
32
384XA
384XB
64
192-499
(499)