Daikin VRV RXYQ72-384XAYCA Service Manual page 300

Heat pump 60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code
Note(s)
1. Fan motor connectors
Fan motor
M1F
M2F
Reference
CHECK 16 Refer to page 372.
293
A
The fan
cannot be
rotated by hand when
YES
disconnecting the
connector from the
fan motor.
NO
Resistance
between the fan
motor power supply cable
YES
terminal and the motor
frame (metallic part) is
less than
1 M:.
NO
CHECK 16
Check for the connector (power
supply cable) of the fan motor.
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost
balance or short circuit is
caused between U, V,
W phases.
NO
Turn ON the power supply to check for the HAP lamps on the fan
PCB.
The HAP
lamp on the fan
PCB does not blink.
NO
PCB
Connector
A6P
X1A
A5P
X1A
U
V
W
(Red) (White) (Black)
{
{
{
YES
YES
SiUS342004EB
Replace the relevant fan motor
(M1F, M2F).
Replace the relevant fan motor
(M1F, M2F).
Replace the relevant fan motor
(M1F, M2F).
Replace the fan PCB (A5P, A6P).
Replace the relevant fan motor.
(M1F, M2F)
Part 6 Service Diagnosis