SiUS342004EB
[2-62]:
Adjust cooling and heating system operation to achieve stable capacity.
Note(s)
This setting may result in a longer reaction time to large load variations.
[2-64]:
Conditions/rules apply for this setting. Refer to selection software or contact your Daikin sales
representative for further details.
[2-81]:
Change [2-81] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].
When [2-81] is set to 0, the original refrigerant temperature target based on [2-8] is kept without
any correction, unless for protection control.
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 201.
Part 5 Field Settings and Test Operation
Cooling and heating capacity learning control
Default value: 0.
Value
[2-62]
0 (default)
1
2
3
Phased installation setting
Default value: 0
Value
[2-64]
0 (default)
1
Single module to dual module installation
2
Dual module to triple module installation
Cooling comfort setting for VRT control
Default value: 1
Value
[2-81]
0
1 (default)
2
3
Description
OFF
Cooling adjustment
Heating adjustment
Cooling and heating adjustment
Description
OFF
Cooling comfort setting
Eco
Mild
Quick
Powerful
Field Settings for Outdoor Unit
190