Daikin VRV RXYQ72-384XAYCA Service Manual page 195

Heat pump 60 hz
Table of Contents

Advertisement

SiUS342004EB
[2-32]:
Change [2-32]: 0,1 or 2 in function of required limitation.
[2-34]:
Note(s)
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set
temperature) is less than 1.5°C (2.7°F).
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set
temperature) is 3°C (5.4°F) or more.
[2-35]:
Part 5 Field Settings and Test Operation
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value: 0 (OFF).
Value
[2-32]
0 (default)
1
2
Indoor fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air
temperature for energy saving
Value
[2-34]
0 (default)
Fan speed is limited to L tap when indoor units capacity  130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity  130%.
Fan speed follows the setting of remote controllers (not limited by indoor units
2
connection capacity).
Limited in cooling when Ta < 29.5°C (85.1°F) and Indoor condition is in condition A
3
(1)
Returned when Ta > 32.5°C (90.5°F) or Indoor condition is in condition B (2)
Limited in cooling when Ta < 23.5°C (74.3°F) and Indoor condition is in condition A
4
(1)
Returned when Ta > 26.5°C (79.7°F) or Indoor condition is in condition B (2)
Limited in cooling when Ta < 19.3°C (66.7°F) and Indoor condition is in condition A
5
(1)
Returned when Ta > 22.3°C (72.1°F) or Indoor condition is in condition B (2)
Limited in cooling when Ta < 29.5°C (85.1°F)
6
Returned when Ta > 32.5°C (90.5°F)
Limited in cooling when Ta < 23.5°C (74.3°F)
7
Returned when Ta > 26.5°C (79.7°F)
Limited in cooling when Ta < 19.3°C (66.7°F)
8
Returned when Ta > 22.3°C (72.1°F)
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (130 ft), the setting [2-35]
should be changed to 0.
Restriction reference
Function not active
Follows [2-30] setting
Follows [2-31] setting
Indoor fan tap setting
Field Settings for Outdoor Unit
188