Juniper MX2010 Manual page 75

Universal routing platform
Hide thumbs Also See for MX2010:
Table of Contents

Advertisement

6.
Using both hands, push firmly on both spring-loaded levers until the PDM is fully seated in the
chassis slot. The PDM faceplate should be flush. Tighten both captive screws.
NOTE: Make sure that the DC circuit feed switch on the PDM faceplate matches the
current rating amperage—60 Aor 80 A. This switch applies to all inputs of this PDM, and
selecting 60 A reduces the available power output capacity of the PSMs supplied by this
PDM.
7.
Loosen the captive screws on the clear plastic cable restraint protecting the terminal studs on the
faceplate of the PDM.
8.
Secure each power cable lug to the terminal studs, first with the flat washer, then with the split
washer, and finally with the nut. Apply between 23 lb-in. (2.6 Nm) and 25 lb-in. (2.8 Nm) torque to
each nut (see
Figure 41 on page
controlled driver or socket wrench.)
Table 9 on page 72
a. Attach the positive (+) DC source power cable lug to the RTN (return) terminal.
b. Attach the negative (–) DC source power cable lug to the –48V (input) terminal.
Table 9: MX2010 DC Power System Input Voltage
Item
DC input voltage
73). Do not overtighten the nut. (Use a 7/16-in. [11 mm] torque-
describes the DC operating range specifications.
Specification
Operating range: –40 through –72 VDC
72