NOTE: The three-phase delta AC PDM must be installed and secured in the chassis before
connecting the power input cables. If the PDM must be removed, both input power cables
must be uninstalled and removed from the PDM before the PDM can be removed from the
chassis. The MX2010 chassis is not sensitive to phase rotation sequence—either clockwise
or counter clockwise will operate correctly.
To connect wires to the terminal block that serves six PSMs:
a. Insert the grounding wire into the grounding point labeled GND.
b. Insert the wire labeled L1 into the input terminal labeled A1.
c. Insert the wire labeled L2 into the input terminal labeled B1.
d. Insert the wire labeled L3 into the input terminal labeled C1.
Figure 35: Connecting Power to a Three-Phase Delta AC Power Distribution Module