Maximum
Specifications
altitude
Operating
3048 m (10,000 ft).
Storage
12,000 m (39,370 ft).
Operating
Specifications
temperature de-
rating
Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft)
The following section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution are beyond the specified limits and cause equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Particulate
Specifications
contamination
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
Corrosive dust
Gaseous
Specifications
contamination
Copper coupon
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
corrosion rate
Silver coupon
<200 Å/month as defined by AHSRAE TC9.9.
corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
NOTE:
Applies to data center environments only. Air filtration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
NOTE:
Applies to data center and non-data center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
Applies to data center and non-data center environments.