Produced Heat; Consumed Energy - Daikin EPRA16DAW1 Installer's Reference Manual

Hide thumbs Also See for EPRA16DAW1:
Table of Contents

Advertisement

5
|
Application guidelines

5.5.1 Produced heat

5.5.2 Consumed energy

Installer reference guide
50
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
INFORMATION
If glycol is present in the system ([E‑0D]=1]), then the produced heat will NOT be
calculated, nor will it be displayed on the user interface.
The produced heat is calculated internally based on:
-
The leaving and entering water temperature
-
The flow rate
-
The power consumption of the booster heater (if applicable) in the domestic
hot water tank
Setup and configuration:
-
No additional equipment needed.
-
Only in case a booster heater is present in the system, measure its capacity
(resistance measurement) and set the capacity via the user interface. Example:
If you measure a booster heater resistance of 17.1Ω, the capacity of the heater
at 230 V is 3100 W.
You can use the following methods to determine the consumed energy:
Calculating
Measuring
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater)
and measuring the consumed energy (example: for outdoor unit). If you do so, the
energy data will be invalid.
Calculating the consumed energy
The consumed energy is calculated internally based on:
-
The actual power input of the outdoor unit
-
The set capacity of the backup heater and booster heater (if applicable)
-
The voltage
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01