9
|
Configuration
Installer reference guide
168
The tank will heat up until the storage comfort temperature has been reached. It
is the higher desired temperature when a storage comfort action is scheduled.
Additionally, a storage stop can be programmed. This feature puts a stop to tank
heating even if the setpoint has NOT been reached. Only program a storage stop
when tank heating is absolutely undesirable.
#
Code
[5.2]
[6-0A]
Eco setpoint
The storage economic temperature denotes the lower desired tank temperature.
It is the desired temperature when a storage economic action is scheduled
(preferably during day).
#
Code
[5.3]
[6-0B]
Reheat setpoint
Desired reheat tank temperature, used:
in Schedule + reheat mode, during reheat mode: the guaranteed minimum
tank temperature is set by the Reheat setpoint minus the reheat hysteresis.
If the tank temperature drops below this value, the tank is heated up.
during storage comfort, to prioritize the domestic hot water preparation. When
the tank temperature rises above this value, domestic hot water preparation and
space heating/cooling are executed sequentially.
#
Code
[5.4]
[6-0C]
Schedule
You can set the tank temperature schedule using the schedule screen. For more
information about this screen, see
Heat up mode
The domestic hot water can be prepared in 3 different ways. They differ from each
other by the way the desired tank temperature is set and how the unit acts upon it.
#
Code
[5.6]
[6-0D]
See the operation manual for more details.
Description
Comfort setpoint:
30°C~[6‑0E]°C
Description
Eco setpoint:
30°C~min(50,[6‑0E])°C
Description
Reheat setpoint:
30°C~min(50,[6‑0E])°C
"9.3.7 Schedule screen:
Description
Heat up mode:
0: Reheat
only: Only reheat operation is
allowed.
1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
4
Example" [
 129].
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01