Daikin EPRA16DAW1 Installer's Reference Manual page 191

Hide thumbs Also See for EPRA16DAW1:
Table of Contents

Advertisement

EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
#
[9.9.9]
[5-09]
[9.9.A]
[5-0A]
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
Priority heater
#
[9.9.D]
[4-01]
Note: In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.
In case power consumption control is ENABLED, the setting [4‑01] defines the
priority of the electrical heaters depending on applicable limitation.
BBR16
See
"5.6.4  BBR16 power limitation" 
functionality.
INFORMATION
Restriction: BBR16 settings are only visible when the language of the user interface is
set to Swedish.
Code
Limit 1: 0 kW~20 kW
Limit 2: 0 kW~20 kW
Limit 3: 0 kW~20 kW
Limit 4: 0 kW~20 kW
Code
Power consumption control DISABLED
[4‑08]=0
0 None : Backup heater and booster heater
can operate simultaneously.
1 Booster heater: The booster heater is
prioritised.
2 Backup
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
0 None : Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
1 Booster
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
2 Backup heater: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
4
[
  57] for detailed information about this
9
Configuration
|
Description
Description
heater: The backup heater is
heater: Depending on the
Installer reference guide
191