Daikin EPRA16DAW1 Installer's Reference Manual page 43

Hide thumbs Also See for EPRA16DAW1:
Table of Contents

Advertisement

EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
A
A
Main leaving water temperature zone
B
One single room
a
Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
b
Non-return valve (field supply)
c
Shut-off valve (field supply)
d
Auxiliary boiler (field supply)
e
Aquastat valve (field supply)
NOTICE
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat  pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
Install non-return valves.
Make sure to only have one expansion vessel in the water circuit. An expansion
vessel is already pre-mounted in the indoor unit.
Install the digital I/O PCB (option EKRP1HBAA).
Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See
4
source" [
 115].
To setup the heat emitters, see
4
system" [
 29].
Configuration
Via the user interface (configuration wizard):
Set the use of a bivalent system as external heat source.
Set the bivalent temperature and hysteresis.
5
B
e
c
d
c
b
b
"8.3.8  To connect the changeover to external heat
"5.2  Setting up the space heating/cooling
Application guidelines
|
a
Installer reference guide
43

Advertisement

Table of Contents
loading

Table of Contents