Daikin EPRA16DAW1 Installer's Reference Manual page 145

Hide thumbs Also See for EPRA16DAW1:
Table of Contents

Advertisement

EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
#
Code
[2.5]
[1-00]
[1-01]
[1-02]
[1-03]
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4]=2):
Description
Set weather-dependent heating in [2.5] Heating
WD curve:
T t
[1-02]
[1-03]
[1-00]
[1-01]
T
Target leaving water temperature (main zone)
t
T
Outdoor temperature
a
Set weather-dependent heating in [9.l]
Overview field settings:
[1-00]: Low outdoor ambient temperature. –
40°C~+5°C
[1-01]: High outdoor ambient temperature.
10°C~25°C
[1-02]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑01]°C~[9‑00]°C
Note: This value should be higher than [1‑03]
as for low outdoor temperatures warmer water
is required.
[1-03]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower than [1‑02] as
for high outdoor temperatures less warm water
is required.
9
Configuration
|
T a
ambient
temperature.
ambient
temperature.
Installer reference guide
145

Advertisement

Table of Contents
loading

Table of Contents