9.4.2 2-points curve

Installer reference guide
134
Types of weather-dependent curve
There are 2 types of weather-dependent curves:

2-points curve

Slope-offset curve
Which type of curve you use to make adjustments, depends on your personal
preference. See
"9.4.4 Using weather-dependent
Availability
The weather-dependent curve is available for:
Main zone - Heating
Main zone - Cooling
Additional zone - Heating
Additional zone - Cooling
Tank
INFORMATION
To operate weather dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See
Define the weather-dependent curve with these two setpoints:
Setpoint (X1, Y2)
Setpoint (X2, Y1)
Example
Y2
Y1
X1
curves" [
"9.4.4 Using weather-dependent
a
X2
4
 136].
4
curves" [
 136].
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01