5.2.3 Multiple rooms – Two LWT zones
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heat pump convector.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
In this document:
▪
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
▪
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Typical example:
Room (zone)
Living room (main zone)
Bed rooms (additional zone)
5
Application guidelines
|
Value
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
Heat emitters: Design temperature
Underfloor heating:
▪
In heating: 35°C
▪
In cooling: 20°C (only refreshment, no
real cooling allowed)
Heat pump convectors:
▪
In heating: 45°C
▪
In cooling: 12°C
Installer reference guide
39