Screen name
Parameters
Generic
Meter
Continuous
flow detect
Setting
review
Water Saver
Water saver
Regen
regen.
Remote
Remote
signal
regeneration
duration
Cl generation
Low salt
Cl generation
Low salt
Regen
interval
Ref. MKT-IM-018 / C - 08.06.2018
Values
0,1 - 999.9 pulses
per gallon
1 - 1500 pulses
per litre
ON
OFF
Displays a summary of all programmed settings.
OFF
1 - 255 seconds
OFF
OFF
/
ON
Low salt detect.
1 - 255
Regeneration
Installer Manual Fleck 5810 - XTR - Programming
Only available when generic meter type is
selected.
If set ON, gives an alarm if continuous flow is
detected at the outlet.
Set the timing for contact closure in seconds
in order to trigger the regeneration.
This parameter will not be available for filter
regeneration types.
On the valves of series 5810 and 5812,
cl generation/low salt must be set OFF
because the chlorine cell kit managed by the
XTR is not available for those valves.
If set ON, chlorine generation together with
low salt detection will be performed during
brine draw cycle.
If set "Low salt detec.", only low salt detection
will be performed during brine cycle.
Only available when cl generation/low salt is
set ON.
This parameter determines the regeneration
frequency on which there will be chlorine
generation.
Low salt detection will be performed during
regenerations indifferently of the frequency
set for cl generation.
Salt alarm will not avoid scheduled
regenerations to be performed.