Parameter Settings; Base Module Inputs And Outputs - Kohler KD700 Operation

Industrial generator sets
Table of Contents

Advertisement

1.5

Parameter Settings

Controller parameter settings are factory-set and password-protected. Selected settings are shown in Figure 8. If changes are
required, contact your distributor.
Parameter
Preheat duration*
Air-preheater maximum delay (at each start attempt)*
Number of starting attempts
Time between starting attempts
Fault inhibition time in starting phase
Auxiliaries start time
Generators starting maximum delay
(Dead Bus synchronizing)
Generator cooling time
Generator immobilization time
Ventilation time after generator stopped
 Parameter settings not applicable for KD2000-KD4000
Figure 8
Factory Settings
1.6

Base Module Inputs and Outputs

The inputs and outputs on the base module are factory set. See Figure 9 and Figure 10 for base module input and output factory
settings. For optional input/output module settings, see the Accessories section.
Note:
Make customer connections to TB10 in the connection box. See the generator set wiring diagram for details.
Inputs
Digital Inputs
DI0
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
DI13
DI14
DI15
DI16
DI17
Analog Input
AI0-
AI0+
Resistive Input
RES0-
RES0+
Figure 9
APM802 Base Module Input Factory Settings
20
300 s (5 min.)
Factory Setting
Remote Start
Low Fuel Level Switch
Breaker Open Status
Remote Reset
Aux Shutdown
High Fuel Level Switch
Aux Warning
Low Oil Level
Battery Charger Fault
Fuel Leak Alarm
Idle Mode
GFCI Tripped
Remote Speed Adjust Enable
Key Switch Enable
Load Shed Enable
Overcrank Test
Reserved for Factory Use
Emergency Stop
Remote Speed Adjust
(+/- 10 VDC)
Ambient Air Temperature
Setting
0 s
30 s
3
15 s
10 s
5 s
5 s
5 s
10 s
TP-7070
11/22