Changing System Settings - Kohler 48RCLC Installation Manual

Residential/light commercial generator set
Table of Contents

Advertisement

Figure 40
12-Lead Generator Reconnection, 2 of 2

7.4 Changing System Settings

The RDC2 controller's keypad and display allow the installer to check and change the generator system settings, if necessary.
The system settings for each generator model are set at the factory and should not normally require changes. Check the genset
system settings and change them, if necessary, after generator reconnection or controller replacement.
The following procedure explains how to change the system settings. The procedure is also illustrated in Figure 43.
Procedure to Change System Settings
1.
Press the Select button to enter the main menu. See Figure 41 and Figure 42. The Overview screen will be displayed.
2.
Press the down arrow button to navigate to the Genset System menu. See Figure 42.
3.
Press the Select button to enter the Genset System menu. See Figure 43.
4.
Press the down arrow button to step through the generator set system settings to the setting that you wish to change.
5.
When the setting is displayed (for example, System Voltage), press the select button. The value will flash.
6.
Press the up or down arrow buttons to increase or decrease the setting.
7.
When the desired setting is shown, press Select. The value stops flashing and the new setting is saved.
8.
Press the down arrow to step to the next setting.
9.
To exit, press the down arrow button until Return is displayed. Press the Select button to exit the menu.
10. Press the AUTO or OFF button to exit the main menu.
Note:
If no buttons are pushed, the controller exits the menus and returns to the generator set status display after 5 minutes.
Display
AUTO button
Figure 41
RDC2 Controller User Interface
TP-7203
4/23
ADV-5875C-AC
Select button
GM77569