1.5 Parameter Settings
Controller parameter settings are factory-set and
password-protected. Selected settings are shown in
Figure 1-6. If changes are required, contact your
distributor.
Parameter
Preheat duration*
Air-preheater maximum delay
(at each start attempt)*
Number of starting attempts
Time between starting attempts
Fault inhibition time in starting phase
Auxiliaries start time
Generators starting maximum delay
(Dead Bus synchronizing)
Generator cooling time
Generator immobilization time
Ventilation time after generator stopped
* Parameter settings not applicable for KD2000- KD4000
Figure 1-6 Factory Settings
TP-7070 8/20
Setting
0 s
30 s
3
15 s
10 s
5 s
5 s
300 s
(5 min.)
5 s
10 s
Section 1 Specifications and Features
17