2.10.1 Faults and Alarms

Press the Alarm (⚠) button shown in Figure 37 to view a list of generator set events, including status messages, alarms, and
faults.
A status message communicates the state of the generator set (example: appearance of Stop mode).
An alarm (warning) signals an impending problem (example: coolant temperature alarm). The alarm button flashes
orange. See Figure 38. A warning (alarm) appears in orange on the screen and does not cause the generator to shut
down.
A fault shuts down the generator set (example: oil pressure fault). The alarm button flashes red. See Figure 39. A fault
appears in red on the screen and causes the generator to shut down (instantly or delayed, depending on the
programmed incidence).
A number on the alarm button indicates the number of active faults and/or alarms.
There are some exceptions. A specific fault message on the HMI screen may be processed as an alarm by the PLC, so there is
no engine shutdown.
Press the stop horn button. The horn (if equipped) turns off and the stop horn button disappears. The alarm button stops flashing
and turns orange.
Press the alarm (⚠) button. A list of the last three active alarms that have not been reset is displayed. See Figure 40. Alarms
and faults are listed in chronological order.
Figure 37
Alarm Button
Figure 38
Appearance of an Alarm (warning)
42
Alarm button
Alarm (⚠) button is orange
Stop horn button
33508003101
TP-7070
11/22