Analog Input/Output Module - Kohler KD700 Operation

Industrial generator sets
Table of Contents

Advertisement

4.4.1

Analog Input/Output Module

The Analog Input/Output (I/O) Module provides two output connections and four input connections. See Figure 92 for I/O
specifications and Figure 93 for connections.
The factory default input and output settings are undefined. I/O settings can be loaded by an authorized service technician.
Contact your Kohler distributor with your requirements for inputs and outputs.
Input/Output
Specifications
0-20 mAmps
Input
Impedance 100 ohms
0-20 mAmps
Output
100-600 ohms
Figure 92
Analog Input/Output Specifications
Figure 93
Analog Input/Output Module
LED
Description
1
Power LED
2
Can bus 1 Communication LED
Figure 94
Module Diagnostic LEDs
TP-7070
11/22
Connection
2
0.75 to 1.5 mm
2
0.75 to 1.5 mm
LED Operation
Green: The module is correctly powered.
Off: Module is not powered.
Flashing green: CAN communication is consistent.
Steady green: No CAN communication.
Off: No CAN communication.
Factory connections or settings
Analog output connections 0 and 1
Analog input connections 0 - 3
31613391201/301/401