2.11.9 Save Parameters

1.
Insert a USB key into the port on the bottom of the HMI module. See the USB Port Location on HMI Module figure.
2.
Press on the Save Parameters icon; the screen shown in Figure 66. Saving starts automatically. When it is completed,
the screen confirming that the save operation was performed successfully appears.
3.
Press on OK to close the window.
Figure 66
Save Parameters Windows
On the USB stick, four files are saved in a directory called case number:
Parameters (file *****_params.x208)
Traceability (file *****_apm_info.i208)
Events (file *****_events.txt)
Curve data (file *****_curve_data.csv)
where ***** is: 0_gs1_<genset serial number>_.

2.11.10 Upload Parameters

An authorized service technician can obtain and load parameter files following the instructions in the controller service manual.
Parameter files are specific to the individual generator set, as identified by the generator set serial number. Do not attemp t to
load parameters that have been saved from a different generator set.