4.4.3

Thermocouple Input Module

Up to three thermocouples can be connected to the Thermocouple Module. Type K or PT100 thermocouples can be connected.
See Figure 99 for thermocouple specifications. See Figure 101 and Figure 102 for connections.
Medium voltage (larger than 600 volts) units are equipped with two thermocouple modules with the settings shown in
Figure 100.
Temperature data can be viewed using the Custom View button on the controller. See the Custom View Button section. If no
thermocouple modules are installed, all temperatures will display 32°F (0°C). If nothing is connected to a channel on a
thermocouple module, -58°F (-50°C) is displayed.
Thermocouple Type
PT100
K Thermocouple
Figure 99
Thermocouple Types and Connections
Thermocouple Module 1
Phase A Temp
Phase B Temp
Phase C Temp
Figure 100 Thermocouple Module Default Settings for Medium Voltage Generators
Figure 101 Thermocouple Module
TP-7070
11/22
Temperature Range
0-200°C (32-392°F)
-20-1000°C (-4-1832°F)
Thermocouple Module 2
Front Bearing Temp
Rear Bearing Temp
User PT100 Temp
Connection
2
0.75 to 1.5 mm
2
0.75 to 1.5 mm
Factory connections or settings
Thermocouple connections 0 - 2, Type K or PT100
31613391201/301/401