Confirming the indoor unit addresses and the position of an indoor unit
using the remote controller
Confirming the numbers and positions of indoor units
To know the indoor unit addresses though position of the indoor unit is recognized
When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one),
or it is a group-controlled one.
<RBC-AWSU5∗ ∗ ∗ ∗ ∗ >
Filed setting menu (1/3)
1. Test mode
2. Register service info.
3. Alarm history
4. Address
5. Monitor function
(1)
(2)
1
Push [
Menu] to open the "Menu"
2
Push and hold [
same time to open "Field setting menu"
→ Push and hold 4 seconds.
3
Select "Indoor unit address" from
"Address" in the "Field setting menu", and
push [
Set/Fix]
→ Screen (1) is displayed, the fans and louvres of all
indoor units in the group operate.
→ The indoor unit that is operating is connected in a
group.
4
In screen (1), push [
→ Each push of [
group → Header unit → Follower unit 1 ...
5
Check the position of the indoor unit
→ Screen (2) is displayed, the fans and louvres of the
selected indoor units operate, the other units stop.
6
After checking, push [
→ Return to the "Address" screen.
– 75 –
Menu] and [
] at the
Menu]
Menu] displays in order: Entire
Return]