Toshiba MMU-UP0071MH-UL Service Manual page 160

Hide thumbs Also See for MMU-UP0071MH-UL:
Table of Contents

Advertisement

No. Part name
2. Attachment
Fan motor
(Continued)
Following to works of 1 of
as original in the reverse procedure.
* When attaching the fan motor reinforcement plate, be sure
that the fan motor reinforcement plate is not caught in the
motor band.
* When attaching the fan motor reinforcement plate, be
careful to the direction of the fan motor reinforcement
plate.
* When attaching the Silocco fan, meet the fixing screw for
Silocco fan to the notch position on the shaft of the fan
motor.
* After fixing the fan case, adjust the position of Silocco fan
at the center of the fan case from side of the discharge
port so that the Silocco fan does not hit to the fan case.
* For the tightening torque of the screw fixing the Silocco
fan, control between 3.7 to 3.8 ft•lbs (5.0 to 5.2 N•m).
Procedure
and 1) to 8), attach the parts
– 160 –
Remarks
Fixing band
Fan motor
lead wire
Lead cover
Fan motor
lead wire
Fixing band
Grand lead wire
Silocco fan fixing screw
Silocco fan
Fixing band
Shaft

Hide quick links: