11-3. Floor Console Exposed

WARNING
Be sure to stop operation of the air conditioner before
work and then turn off switch of the breaker.
No. Part name
1. Detachment
Electric
parts
1) Remove the suction grilles (2 pieces).
assembly
(No screw fixing)
2) Remove the wire guard.
(M4 screw: 4 pieces)
3) Remove the front panel.
(M4 screw: 2 pieces)
4) Remove the discharge grille.
(M4 x 0.8" (20mm): 2 pieces)
5) Remove the switch box.
(M4 screw: 3 pieces)
6) Take off the fan motor lead from the clamp, slide the
glass tube, and then remove the relay connector.
7) Take off the TA sensor from the clamp.
8) Take off the connectors of TC1, TC2, and TCJ sensors
from P.C. board.
CN100 ... TC1 (3P: Brown)
CN101 ... TC2 (2P: Black)
CN102 ... TCJ (2P: Red)
* Unlock the lock of the housing part, and then remove
9) Remove the relay connector of the PMV lead.
10)Remove body of the electric parts assembly.
(M4 screw: 1 piece)
2. Attachment
Following step 1 of
original in the reverse procedure.
Procedure
the connectors.
and 1) to 10), attach the parts as
CAUTION
Be sure to put on gloves during working time;
otherwise an injury will be caused by a part etc.
Electric parts
assembly
Clamp
Clamp
– 147 –
Remarks
Relay
TC1, TC2, TCJ
connector
sensors
(PMV lead)
Fan motor lead
M4 screw
Relay connector
TA sensor
(Fan motor lead)
Glass tube