No.
Item
6
Fan speed
1) By the command from remote control, fan speed is
selection
2) When the fan speed mode [AUTO] is selected, the fan
<COOL>
• Fan speed mode [AUTO] in case when remote
• If the fan speed has been changed once, it is not
• When cooling operation has started, select a down-
• If the temperature is just on the difference boundary,
<HEAT>
(+0.9) +1.8 [(+0.5) +1.0]
(–0.9) –1.8 [(–0.5) –1.0]
(–1.8) –3.6 [(–1.0) –2.0]
(–2.7) –5.4 [(–1.5) –3.0]
(–3.6) –7.2 [(–2.0) –4.0]
( ) : indicate the value when the remote control
• If the fan speed has been changed once, it is not
• When heating operation has started, select an upward
• If the temperature is at the difference boundary, the
• If TC2 ≥ 140°F (60°C), the fan speed increases by 1 step.
Outline of specifications
changed. ((HH), (H+), (H), (L+), (L) or [AUTO])
speed varies by the difference between TA and Ts.
TA-Ts °F (°C)
+5.4 (+3.0)
HH
+4.5 (+2.5)
<HH>
+3.6 (+2.0)
H+ <HH>
+2.7 (+1.5)
H <HH>
+1.8 (+1.0)
L+ <H+>
+0.9 (+0.5)
L <H>
Tsc
L <H>
–0.9 (–0.5)
L <L+>
< > : Indicate automatic cooling.
control sensor works is equal to that in case when
indoor unit sensor works.
changed for 3 minutes. However when the air volume
is changed, the fan speed changes.
ward slope for the fan speed, that is, the high position.
the fan speed is not changed.
Ts-TA °F [°C]
(0) Tsh
Indoor unit sensor works.
Remote control sensor works.
sensor is worked.
changed for 1 minute. However when the fan speed
changed, the fan speed changes.
slope for the fan speed, that is, the high position.
fan speed is not changed.
A
B
C
D
E
F
G
L <L+>
L+ <H>
H <H+>
H+
<HH>
HH
<HH>
< > : Indicate automatic heating.
– 30 –
Remarks
HH > H+ > H > L+ > L > UL
Depends on fan speed mode
selection at the remote controller.
(H+) and (L+) cannot be selected.
For Floor Console Exposed
type, or Floor Console
Recessed Type,, (HH), (H), (L)
or [AUTO] can be selected
regardless of remote controller
models.
Set data [32]
0000: Indoor unit sensor
(Main unit)
0001: Remote control sensor
E
D
C
B
A
TC2: Temperature of indoor
heat exchanger sensor