Toshiba MMU-UP0071MH-UL Service Manual page 39

Hide thumbs Also See for MMU-UP0071MH-UL:
Table of Contents

Advertisement

No.
Item
22
Occupancy
sensor
23
Soft cooling
24
Dual set point
(AUTO mode)
Outline of specifications
1) During the Occupancy sensor operation when there is no
people in the Occupancy sensor range, it is automatically
switched to the operation for the absence.
2) The Occupancy sensor operation can change by selecting
13. Occupancy sensor in the remote controller menu as
follows, and operates according to the operation at absent
time, if time or absence of the setting contents continues.
However time counting starts after the room temperature is
stabilized. (after for 30 minutes operation)
Item
Invalid
Enable
3) The operation at absent time can be changed by selecting
13. Occupancy sensor in the remote controller menu.
Item
Standby
Stopped
4) If the operation at absent time stops during group operation,
or absence is fixed in each system, the operation starts
circular operation once, and then the operation stops when
absence was determined on all group.
* Wired remote controller : RBC-AWSU5∗ is required.
1) Sensation of draft can be suppressed by controlling
performance and correcting the louver angle during cooling
operation.
2) However, it may not cool well because the operation will be
performed with the cooling capacity suppressed.
3) Perform operations from the remote controller menu to use
soft cooling.
1) The temperature for heating operations and cooling
operations can be set separately in AUTO mode when dual
set point is valid.
2) The compressor will turn off (thermostat-OFF) when
reaching the set temperature for heating operations and
cooling operations.
3) Set CODE No. (DN) [77] to enable Dual set point.
DN [77]
Data
0000
0002
Setting contents
Invalid
30 minutes to 150 minutes
(30 minutes each)
Operation at absent time
Circulator
Operation stop
Dual set point
Unavailable (Factory default)
Available
– 39 –
Remarks
The Occupancy sensor
can be set up by wired
remote controller
RBC-AWSU5∗
This can only be used
when the Occupancy
sensor, which is sold
separately, is connected.
This function cannot be
used with remote
controllers that are not
RBC-AWSU5∗.