No. Part name
1. Detachment
Fan
assembly
1) Following step 1 of
parts.
2) Take off the nut which fixes the fan assembly.
(M6 nut: 1 position)
3) Draw out the fan assembly toward you.
(M4 screws: 4 pieces)
2. Attachment
Following step 1 of
original in the reverse procedure.
1. Detachment
Fan motor
1) Following step 1 of
2) Take off the capacitor lead from the capacitor.
(M4 screws: 2 pieces)
3) Take off the screws at (right) and (left) of the fan case.
(M4 screws: 8 pieces, M4 x 0.47" (12mm): 4 pieces)
4) Remove the fan case at the outside.
5) Loosen screws of the Silocco fan to remove the
Silocco fan.
6) Loosen the fixing screws of the fan motor, and then
remove the fan motor.
(M4 x 0.47" (12mm): 2 pieces)
2. Attachment
Following step 1 of
original in the reverse procedure.
* When attaching the Silocco fan, meet the fixing screw for
Silocco fan to the notch position on the shaft of the fan
motor.
* After fixing the fan case, adjust the position of Silocco fan
at the center of the fan case from side of the discharge
port so that the Silocco fan does not hit to the fan case.
* For the tightening torque of the screw fixing the Silocco
fan, control between 3.7 to 3.8 ft•lbs (5.0 to 5.2 N•m).
Procedure
, 1) to 3), 6 )and 7), detach the
, and 1) to 3), attach the parts as
and 1) to 3), detach the parts.
and 1) to 5), attach the parts as
Screw fixing
Silocco fan
Silocco fan
M4 screw
Capacitor
Capacitor
lead
Capacitor
cover
Shaft
Fan case
– 150 –
Remarks
M4 screw
M6 nut
Fan case (Right), (Left)
Silocco fan
Screw fixing Silocco fan
Fan motor
Motor band
Discharge port
Fan case
Silocco fan