Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
01: TK1 oil
circuit trouble
02: TK2 oil
circuit trouble
H16
H16
1∗: Compressor
1 side
2∗: Compressor
2 side
H17
H17
Detected indoor
unit address
L02
L02
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
Location
Description
of
detection
I/F
Oil level
detection
circuit trouble
Compressor
Compressor
P.C. board
trouble
(Step-out)
Indoor unit
Outdoor units
model
disagreement
trouble
Indoor unit
Duplicated
indoor header
unit
I/F
Duplicated
outdoor line
address
I/F
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor unit
Connection of
group control
cable to
standalone
indoor unit
Indoor unit
Indoor group /
addresses not
set
Indoor unit
Indoor capacity
not set
Check code detection
System status
condition(s)
All stop
No temperature change is
detected by TK1 despite
compressor 1 having been
started.
No temperature change is
detected by TK2 despite
compressor 2 having been
started.
All stop
Compressor is in step-out
condition.
Stop of
In case of different outdoor
corresponding
unit (Not corresponded to
unit
Air to Air Heat Exchanger
type)
Stop of
There are more than one
corresponding
header units in group.
unit
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
All stop
More than one indoor units
have been set up as priority
indoor unit.
All stop
More than one indoor units
have been set up as priority
indoor unit.
Stop of
There is at least one
corresponding
standalone indoor unit to
unit
which group control cable is
connected.
Stop of
Address setting has not
corresponding
been performed for indoor
unit
units.
Stop of
Capacity setting has not
corresponding
been performed for indoor
unit
unit.
– 106 –
Check items (locations)
• Check for disconnection of
TK1 sensor.
• Check resistance
characteristics of TK1
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
• Check for disconnection of
TK2 sensor.
• Check resistance
characteristics of TK2
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check SV3F valve
malfunction.
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
• Check power supply
voltage. (AC380V ± 10%).
• Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (compressor).
• Check outdoor unit model.
(Check whether the
outdoor unit corresponds
to Air to Air Heat
Exchanger type or not.)
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
• Check line addresses.
• Check display on priority
indoor unit.
• Check displays on priority
indoor unit and outdoor
unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Set indoor capacity. (DN =
11)