Manual address setting using the remote controller
Procedure when setting indoor units' addresses first under the condition that indoor wiring has been completed
and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
Indoor unit 1
Remote
controller
Line (system) address
Indoor unit address
Group address
In the example above, disconnect the remote controller connections between the indoor units
and connect a wired remote controller to the target unit directly before address setting.
<RBC-AWSU5∗ ∗ ∗ ∗ ∗ >
1
Push [
Menu] to open the "Menu".
2
Push and hold [
→ Push and hold 4 seconds.
3
In the "Field setting menu" screen, push [
push [
Set/Fix].
4
Push [
] and [
→ "Indoor unit" was selected, the fans and louvres of the indoor units operate.
unit
Indoor unit 2
1
1
1
2
1
2
Header unit
Follower unit
6.Setting louver position
7.Setting timer operation mode
8.Easy I.DN setting
9.DN setting
10.Reset Power Consumption data
Menu] and [
] at the same time to open "Field setting menu".
] to select "Indoor unit", and the push [
Refrigerant line 2
Outdoor
unit
Indoor unit 3
Indoor unit 1
1
3
2
Follower unit
Follower unit
Menu(1/3)
] and [
– 71 –
Indoor unit 2
2
2
1
2
2
2
Follower unit
] to select "DN setting", and then
Set/Fix].