Configure Data Logger; Set Up Hardware; Set Up Loggernet - Campbell CELL200 Series Product Manual

4g lte cellular module
Hide thumbs Also See for CELL200 Series:
Table of Contents

Advertisement

NOTE:
This setting does not affect outbound connections, only incoming connections.
Staying on the Settings > Serial Mode Setup tab, enter your trusted IP addresses, one per
line, in the Trusted IP Host Addresses box.

8.4.5.2 Configure data logger

1. Connect to your data logger by using Device Configuration Utility.
2. On the PPP tab, set Config/Port Used to Inactive.
3. When using RS-232 serial server mode, it is recommended that you use a fixed baud rate
on the data logger RS-232 port. On the Com Ports Settings tab, select the RS-232 port and
set the Baud Rate to the fixed option to match the RS 232 baud rate set in the CELL200-
series module.
4. If using CS I/O communication, the throughput can be enhanced by changing the SDC
Baud Rate from 115200 to 460800. On the Advanced tab, set the SDC Baud Rate to 460800.
Note that if there are other devices on the CS I/O port, they all must be able to support this
higher baud rate.

8.4.5.3 Set up hardware

1. Connect the cellular antenna, if it is not already connected. When using a MIMO antenna
with multiple cellular connections, connect the primary cable to Cellular and the secondary
to Diversity. If the cables are not marked in this way, they can be connected to either
antennna port.
2. Connect your data logger RS-232 or CS I/O port to the CELL200-series module RS-232 or
CS I/O port. Ensure the same port is used for each device, for example RS-232 to RS-232.
See
Wiring and
3. If not connecting through CS I/O, provide power to the CELL200 series. The data logger
provides power through the CS I/O port. USB power is not sufficient to power the CELL200
series; 12 V is required.

8.4.5.4 Set up LoggerNet

The LoggerNet Network Map is configured from the LoggerNet Setup screen.
NOTE:
Setup has two options, EZ (simplified) and Standard. Click on the View menu at the top of the
Setup screen, and select Standard view.
connections (p. 29).
CELL200-Series 4G LTE Cellular
Module     57

Advertisement

Table of Contents
loading

Table of Contents