To Configure the Modbus Settings

7.17 To Configure the Modbus Settings
1. On the CLSS Gateway board, find the S6 button.
2. Press the S6 button for a minimum of 6 seconds and then release it. It will switch the
gateway to configuration mode.
The LED indicator DL3 turns ON and SOLID indicating that the configuration is
enabled.
3. Connect the Ethernet cable to Eth0 for enabling web configuration.
NOTE: The web configuration is available only on Eth0.
4. Open the Configuration Computer connected to the Eth0 port of the gateway.
NOTE: The static IP of the Eth0 port is 192.168.10.190.
5. In the Chrome browser, enter the following URL:
https://192.168.10.190:9443/config/index.html
6. Do the following if any security warning is shown. Otherwise, go to step 7.
1. Click the Advanced link below the error message.
2. Agree to proceed.
7. In the Gateway Configuration Tool page, enter the password.
NOTE: The default password is: Welcome123
8. Go to the Network Settings in the Gateway Settings section.
9. Assign the Eth1 port with a static IP address for the Modbus connection.
10.Connect the Ethernet cable between the Eth1 port of CLSS gateway and its LAN
device.
11.Find and click Modbus Settings in the Gateway Settings section.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Modbus Communications
54