C.8.3: Vigilon Series Panels; To Use A Uart/Ttl Connection; To Use An Rs-232 Port Via An I/O Card - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

Gent Panels
C.8.3 Vigilon Series Panels
For a fixed gateway, we recommend using a UART/TTL connection. If it is not available,
use a RS-232 connection.

To Use a UART/TTL Connection

1. On the Gateway Side
Connect the male UART/TTL cable to the Rx (Red), Gnd (Silver), and Tx (White) UART/TTL
terminals of the gateway.
The UART/TTL port is labeled as 5 in
2. On the Panel Side
1. Within the panel, find the backplane PCB board (see
2. Connect the 3.5mm phono socket to the P11 connector on the panel's PCB.
3. Power Connection
On the Gateway Side
Connect the power cable to a 24V DC external power source.
NOTE: The external power supply must be dedicated and not shared with any other
devices.
NOTE: The panel's power supply to the gateway must be within +24V DC power.

To Use an RS-232 Port via an I/O Card

Using an add-on I/O card (VIG-IOC-DOM), certain Vigilon panel variants can
communicate with the CLSS Gateway.
The I/O card has a rotary switch, which should point to 5.
The baud rate of the I/O card should be 19200.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Figure
Figure C.19: Vigilon Panels: UART/TTL Connection
C.2.
Figure
C.19).
Connecting to the Panels
132

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents