Verifying The Central Station Communication Configurations; 3: Dual Path Communication For Alarm Transmission; Supervision Period; Transmission Options - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

Honeywell CLSS Alarm Transmission Services
7. Click on the specific CLSS Gateway of the building.
8. Click on the Connected Gateway activation card inside the selected gateway.
9. Click Configure Now.
10.Select the central station to configure from the central stations list.
11.Follow the on-screen instructions to enable the alarm transmissions.

Verifying the Central Station Communication Configurations

After configuring for the central station communication, call the central station to
confirm that the alarm transmission for the building is activated.
5.4.3 Dual Path Communication for Alarm Transmission
While configuring the central station communication, you can choose a single path or
two paths for alarm transmissions. Reporting options are: LTE cellular only, IP only, IP
Primary with LTE cellular backup, or LTE Cellular Primary with IP backup.
NOTE: Alarms will be sent through two among the following ports: Ethernet, Wireless, or
Cellular.

Supervision Period

Dual paths are monitored for integrity at an interval period as per NFPA 72 requirements.
In case of a failure, both the local premises and the central station receive a failure report
with a unique code as in the central station report.

Transmission Options

CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Path Options
Available Paths
Single Path
2010 Cell
Cellular
2013 Cell
2010 IP
IP
2013 IP
Dual Path
2010 IP & Cell
IP and Cellular
2013 IP & Cell
Supervision Interval
5 Minutes
60 Minutes
5 Minutes
60 Minutes
24 Hours
6 Hours
Configurations
36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents