C.6.3: Programming For Annunciator (Ann-Pri); C.6.4: To Program For Annunciator; To Verify The Changes - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

FireWarden Panels
C.6.3 Programming for Annunciator (ANN-PRI)
Programming enables the panel to recognize the CLSS gateway and the annunciator.
CAUTION: BEFORE PROGRAMMING, ENSURE THAT THE ANN-PRI COMMUNICATION CABLE IS
!
CONNECTED WITH THE PANEL.
C.6.4 To Program for Annunciator
Using the keypad on the panel, you select options on the screens.
1. On the panel, press the Enter button on the keypad.
2. View the panel screen options.
3. On the keypad, press 2 to select 2 = PROGRAMMING MODE.
4. Enter the panel's password in the PROGRAMMING screen.
The default password is: 00000000
5. Press the down arrow button to select 2 = POINT PRGORAM.
6. Select 3 = FUTURE USE and then select 3 = ANNUNCIATORS.
7. Select 1 = PRIMARY on the ANN-BUS SELECT screen.
8. Ensure 1 = ENABLED YES on the ANN PRIMARY screen.
9. Select 2 = MODULES INSTALLED.
10.Select 1 = ADDR. 1-1 NONE on the ANN-BUS MODULES screen.
11.Ensure 1 = TYPE NONE on the ANN-BUS MODULE 1-1 screen.
12.Press the down arrow button once to go back to the ANN-BUS MODULE TYPE screen.
13.Press the down arrow button to go to the next screen.
14.Select 2 = ANN-S/PG MODULE.
15.On the keypad, press the Esc key three times to go back to the ANN/BUS SELECT screen.
16.Select 3 = ANN-BUS OPTIONS.
17.Press 1 = ANN-S/PG OPTIONS on the ANN-BUS screen.
18.Set CLASS A to YES if your ANN Bus wiring is Class A topology, otherwise set it as NO.
19.Ensure the following settings on the ANN-S/PG OPTIONS screen:
1 = PORT PAR
2 = PRINTER SUPV YES
3 = OFFLINE TIMER 0
20.Press the Esc button continuously until the main screen appears.
The panel saves the changes and resets.

To Verify the Changes

It is a good practice to confirm that the panel reflects the changes you did.
1. Use the keypad and go to the ANN-BUS MODULES screen.
2. Check that 1 = ADDR.1-1 ANN-S/PG on the ANN-BUS MODULE 1-1 screen.
3. Check that no ANN primary fault is reported on the main screen.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Connecting to the Panels