IP Requirements

1.7 IP Requirements
1.7.1 IP Port Settings
The following IP ports must be available to the NFN-GW-EM-3:
Port
53
80
123
443
2017
4016
5000
5100
1.7.2 Bandwidth Usage
Worst Case Sustained
Bandwidth
Typical
Maximum
1.7.3 IP Restrictions
The following restrictions apply:
• Must have a static IP address. DHCP is not supported.
• The use of a NAT is not supported.
• Web access via an HTTP Proxy is not supported.
NFN-GW-EM-3 Installation and Operation Manual — P/N LS10017-000NF-E:D1 5/1/2019
Type
Direction
UDP and TCP Out
TCP
In
UDP
Out
TCP
In/Out
TCP
In
TCP
In
TCP
In
TCP
In
No. Workstations
50
50+ Audio
Purpose
DNS resolution:
The optional web portal feature in the NFN-GW-EM-3 must
resolve
www.evanceservices.com
eVance server.
Web Based Configuration
SNTP
HTTPS Communications:
The NFN-GW-EM-3 will accept connections on port 443 for
configuration of the NFN-GW-EM-3. Typically, this incoming
connection is local to the site intranet and not externally from
the Internet.
The optional web portal feature in the NFN-GW-EM-3 will
communicate out to the eVance server on the Internet
(www.evanceservices.com) when configured for eVance
operations.
Connection from Workstation (Events and Commands)
Upgrade for Embedded Gateway
VeriFire Tools Access
Voice Paging
Bandwidth
2520 Bytes/Sec
20160 bit/Sec
0.020 Mb/Sec (Approx.)
14670 Bytes/Sec
117360 bit/Sec