System Trouble; Exception Responses - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

System Trouble

7.28 System Trouble
For information about system trouble information stored in holding registers, refer to
7.23.1 "Panel and System Troubles Holding

7.29 Exception Responses

If a Modbus master device sends an invalid command or attempts to read an invalid
holding register, an exception response is generated. The exception response follows the
standard packet format. The high order bit of the function code in an exception response
is 1. The data field of an exception response contains the exception error code. The table
describes the exception codes sup- ported and the possible causes.
Exception Code
0x01
0x02
0x03
0x0A
0x0B
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table 7.29: Exception Codes
Protocol Identifier in Modbus packet does not match
Modbus protocol. Protocol Identifier in Modbus should
always be "0".
Function code sent by the client is not supported by the
CLSS Gateway or the FACP.
A Control command was sent to the gateway. Contact
customer service.
Register address range specified by the client is not
supported by the FACP.
Register address range requested is valid but the device
(e.g. Detector, Module, Zone, etc.) is not present in the
specified FACP.
Analog Value is requested from a register which is not
associated with a 4–20 mA device.
Number of registers requested exceeds the maximum
allowed limit. The maximum number of registers that a
client can read at one time is 100. The exception to this is
for analog values where the maximum number of
registers a client can read at one time is 10.
Invalid Data written to the register when sending
commands.
Unit ID specified in the request packet is not configured
for monitoring.
FACP is off line or there is a communication problem on
the panel and/or NFN.
Registers".
Conditions
Modbus Communications
Exception Name
Illegal function
Illegal data
address
Illegal data value
Gateway path
failed
Gateway target
failed