3: Standard Object Types Supported-Life Safety Point/Life Safety Zone - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

BACnet Feature Activation
8.6.3 Standard Object Types Supported—Life Safety Point/Life Safety Zone
BACnet
Enumeration
Present
Value
BACnet
Enumeration
Tracking
Value
BACnet
Enumeration
Event State
BACnet
Enumeration
Reliability
BACnet
Enumeration
Mode
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
BACnet
LifeSafetyState
IssQuiet
0
IssPreAlarm
1
IssAlarm
2
IssFault
3
IssActive
7
IssSupervisory
22
BACnet
LifeSafetyState
IssQuiet
0
IssPreAlarm
1
IssAlarm
2
IssFault
3
IssActive
7
IssSupervisory
22
BACnet
LifeSafetyState
EsNormal
0
EsFault
1
EsOffNormal
2
BACnet
LifeSafetyState
reNoFaultDetected
0
re_UnreliableOther
7
BACnet
LifeSafetyState
IsmOff
0
IsmEnabled
11
IsmDisabled
12
NFN State
Normal
PreAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm, (Life/Property), Medical
Emergency
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fire Device or Zone, Disabled, Non-Fire Device
Disabled
Non-Fire Activation
Supervisory (Equipment), Supervisory (Guard's
Tour)
NFN State
Normal
PreAlarm
Fire Alarm, Security Alarm (Life/Property),
Critical Process Alarm (Life/Property), Medical
Emergency
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fire Device or Zone, Disabled, Non-Fire Device
Disabled
Non-Fire Activation
Supervisory (Equipment), Supervisory (Guard's
Tour)
NFN State
Normal
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fireevice Disabled, Non-Fire Device Disabled
All statuses other than normal and fault.
NFN State
All statuses other than trouble.
Security Trouble, Fire Trouble, Non-Fire Trouble
NFN State
Power-Up State
Set if point has been disabled and subsequently
enabled since startup.
Fire Device or Zone Disabled, Non-Fire Device
Disabled
The BACnet Feature
96