To Use a USB Connection

1. On the Gateway Side
Connect the USB-C side of the cable to the USB port of the gateway.
The USB port is labeled as 8 in the figure
2. On the Panel Side
Connect the USB-B side of the cable to the USB port of the panel.
3. Power Connection
In the PB15 terminal on the panel,
Connect the gateway to a 24V DC internal power source of the panel.
NOTE: The external power supply must be dedicated and not shared with any other
devices.
NOTE: The panel's power supply to the gateway must be within +24V DC power.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Figure
Figure C.18: Compact Panels: USB Connection
C.2.
Communica on se ngs
RS232
USB
Connecting to the Panels
Card :
0
Port No. : 1 or 2
Mode:
Standard
Baud Rate: 19200
Card :
0
Port No. : 3
Mode:
Standard
Baud Rate: 38400