C.13: Triga Panels; C.13.1: Connection Options; C.13.2: To Use An Rs-485 Connection - Honeywell HON-CGW-MBB Installation And User Manual

Connected life safety services clss gateway
Table of Contents

Advertisement

Triga Panels
C.13 Triga Panels
C.13.1 Connection Options
The gateway operates only with the Triga fire alarm control panels as listed in the table
below:
CAUTION: WHEN SUPPORTING THE ALARM TRANSMISSION, IT IS RECOMMENDED THAT THE TRIGA
!
PANEL SHOULD USE SECONDARY ANN BUS CHANNEL WITH CLASS A WIRING.
IF THE ALARM TRANSMISSION SERVICE IS NOT USED, THE PANEL CAN USE EITHER THE PRIMARY OR
THE SECONDARY ANN BUS CHANNEL FOR THE CLSS GATEWAY CONNECTION.
Minimum Required Versions
For the Panel: 6.05.01
For the CLSS Gateway: 3.1.4.74
C.13.2 To Use an RS-485 Connection
Using an RS-485 cable the CLSS Gateway connects with the annunciator primary
terminal of the panel.
CAUTION: CONNECT EITHER THE CLSS GATEWAY OR THE ANN S/P G MODULE WITH THE PANEL. BOTH
!
OF THEM SHOULD NOT BE CONNECTED TOGETHER WITH THE PANEL.
1. On the Gateway Side
At the RS-485 A port in the gateway board:
• Connect the A connector to the IN+ pin of the RS-485 A port.
• Connect the B connector to the IN- pin of the same RS-485 A port.
The RS-485 ports in the gateway board are labeled as 3 and 4 in the
2. On the Panel Side
At the S-BUS board in the ANN-BUS PRI terminal:
• Connect the RS-485 +ve wire to the A port.
• Connect the RS-485 -ve wire to the B port.
3. Power Connection
On the Gateway Side
In the power supply port (labeled 7 in the
• Connect the Red wire to the +24V pin.
• Connect the Black wire to the Gnd pin.
On the Panel Side
In the power board of the panel:
• Connect the Red wire to the +ve pin.
• Connect the Black wire to the -ve pin.
CLSS Gateway - Installation and Users' Manual | P/N:LS10248-000HW-E | REV. F | FEB/11/2022
Table C.11: Triga Panel Connection Options
Fire Alarm Panel Models
TR-75R
TR-75B
TR-2100R
TR-2100B
TR-R2100R
TR-R2100B
TR-2100ECSR
TR-2100ECSB
RS-485
UART/TTL
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Figure
C.2):
Connecting to the Panels
RS-232
USB
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Figure
C.2.