Figure 78 Replacement Of Drive In Its Carrier - Seagate Exos X 4006 Series Hardware Installation And Maintenance Manual

Hide thumbs Also See for Exos X 4006 Series:
Table of Contents

Advertisement

Figure 78 Replacement of drive in its carrier

c. Push the DDIC down until the top is flush with the top of the slot.
d. While holding it against the bottom of the slot, slide the top latch toward the rear of the drawer until it locks into place
and the DDIC  release latch locks.
Figure 79 Release latch open and unlocked
Figure 80 Release latch properly locked
e. Verify that all drives are at the same level and all DDIC release latches are properly locked.
CAUTION Do not proceed to close the drawer unless all DDICs are in a fully locked position or DDIC height can
inhibit or completely prevent drawer access once you close it.
f. Confirm that the DDIC fault condition LED is off.
107            Chapter 11   In-service field maintenance for 5U  enclosures