10. Facing the front of the rack cabinet, hand tighten both of the Phillips-head M5 x 15 screws using an 8mm nut driver or a
Philips screwdriver so that the hex head flanges are flush with the front rack post.
11. Fix the adjusted length of the left rail by hand tightening all 4 rail slide set screws using a Phillips screwdriver.
12. Repeat the process for the right rail.

Mount the 5U enclosure into the rack cabinet

WARNING! Serious injury and mechanical failure can result if you do not adhere to rack cabinet safety precautions.
To avoid risk of death or injury from tipping the rack, follow all rack installation guidelines, securing the rack cabinet to the
l
floor with a concrete anchor kit.
To avoid catastrophic failure of the rack assembly, never exceed rack cabinet weight limits.
l
Entirely support the storage enclosure with the mechanical lift until the storage enclosure is in the storage position.
l
Follow local occupational health and safety guidelines and meet all requirements for manual material handling.
l
Mounting the storage enclosure into the rack cabinet is the most critical of the installation procedures and requires your full
attention. Safety and hardware longevity depend on rails' smooth function and correct implementation of this task.
Make sure there is sufficient clearance for a technician and the storage enclosure when a drawer is fully extended.
l
Observe rack cabinet weight limits.
l
Fill the rack cabinet from the bottom to the top, with the heaviest equipment at the bottom.
l
Make your approach with the mechanical lift level, straight, and parallel to the rack cabinet. Any skew, warp, or tilt prevents
l
the storage enclosure from properly resting on the rackmount shelf in the rack cabinet.
Required equipment
Mechanical lift
Storage enclosure with attached inner rails
Rack cabinet with installed outer rails
#2 Phillips-head screwdriver, 6-in length
(Optional) 8mm nut driver, 6-in length
Panhead screw, M5 x 8, #2
Panhead screw, 10-32 X 3/4"
Lock washer, M5, Type B
Washer, M5, 10 x 1.6mm
To mount the 5U enclosure into the rack cabinet:
1. Confirm that the outer rails are properly and securely installed in the rack cabinet.
2. Confirm that the storage enclosure does not contain any drives, so the chassis has empty drawers.
Qty
Identification
1
N/A
1
N/A
1
N/A
1
N/A
1
N/A
4
6
6
6
Chapter 5   Installation of 5U enclosures
40