Types Of Installation - Siemens SIMATIC NET SCALANCE X-200RNA Operating Instructions Manual

Industrial ethernet switches
Hide thumbs Also See for SIMATIC NET SCALANCE X-200RNA:
Table of Contents

Advertisement

6.3

Types of installation

Unless stated otherwise, the mounting options listed below apply to all devices of the type
SCALANCE X-200RNA.
The SCALANCE X-200RNA devices can be mounted in the following ways:
• Installing on a 35 mm DIN rail
• Wall mounting
Note
Mounting on a SIMATIC S7-300 standard rail is not possible.
NOTICE
Do not cover the ventilation grilles
During installation, select a mounting position so that the ventilation grilles are always free to
achieve adequate cooling. In the standard position, the ventilation grilles are on the top and
bottom of the housing; in the case of SCALANCE X204RNA EEC, they are also on the sides of the
housing.
Minimum clearances
If you install the SCALANCE X-200RNA without forced ventilation or cooling, minimum
clearances must be maintained to neighboring devices or the wall of the housing. By keeping to
the minimum clearances, there is then an adequate stream of air for heat dissipation during
operation. Keep to the following minimum clearances to neighboring devices.
Table 6-1
Minimum clearance to devices below the SCALANCE X-200RNA
Minimum clearance to devices above the SCALANCE X-200RNA
Minimum lateral clearance to devices (SCALANCE X204RNA EEC only)
See also
27069465 (https://support.industry.siemens.com/cs/ww/en/view/27069465)
SCALANCE X-200RNA
Operating Instructions, 04/2022, C79000-G8976-C342-07
Minimum clearances when installing in cabinets
Installation and disassembly
6.3 Types of installation
100 mm
100 mm
20 mm
61

Advertisement

Table of Contents
loading

Table of Contents