5.2

Types of installation

The devices can be installed in the following ways:
● Installation on a 35 mm DIN rail
● Installation on a SIMATIC S7-300 standard rail
● Wall mounting
If a device is operated in an ambient temperature between 50 ℃ and 75 ℃, the temperature
of the device housing may be higher than 70 °C. The device must therefore be installed so that
it is only accessible to service personnel or users that are aware of the reason for restricted
access and the required safety measures at an ambient temperature of 50 ℃ to 75 ℃.
Installation clearance
Keep to the minimum clearances so that the convection ventilation of the device is not blocked.
● Below at least 10 cm
● Above at least 10 cm
5.3

Installation on a DIN rail

Installation
To install the device on a 35 mm DIN rail complying with DIN EN 50022, follow the steps below:
1. Place the second housing guide of the device on the top edge of the DIN rail.
2. Press the device down against the DIN rail until the spring catch locks in place.
3. Fit the connectors for the power supply. See also section "Power supply (Page 36)".
4. Fit the connectors for the signaling contacts. See also section "Signaling contacts
(Page 37)".
5. Insert the terminal blocks into the sockets on the device.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10
WARNING
WARNING
Use of the SCALANCE X108PoE in shipbuilding
When used in shipbuilding, mounting the SCALANCE X108PoE on 35 mm DIN rails is not
permitted.
35 mm DIN rails do not ensure sufficient stability when used in shipbuilding.
Assembly
5.3 Installation on a DIN rail
31