Device description

5.9 LEDs

5.9
LEDs
5.9.1

SCALANCE X-200RNA (PRP)

5.9.1.1

Fault LED

If the LED is lit red, a SCALANCE X-200RNA (PRP) has detected an error/fault.
At the same time, the signaling contact opens assuming that the response of the signaling
contact has not been configured differently.
The LED signals that the SCALANCE X-200RNA (PRP) can adopt the following statuses:
Device type SCALANCE
X204RNA (PRP)
X204RNA EEC (PRP)
X204RNA EEC (PRP/HSR)
If configured as PRP device.
1. Link down event on a monitored port.
2. Failure of one of the two redundant power supplies.
3. C-PLUG error.
4. Device startup, the LED is lit for approx. 20 seconds.
5. Internal error.
6. A redundancy error was detected.
7. No problem has been detected by the SCALANCE X-200RNA (PRP).
5.9.1.2

Power LED

The LEDs signal the following statuses of the SCALANCE X-200RNA (PRP).
The status of the power supply is indicated by a green LED:
Device type SCALANCE
X204RNA (PRP)
X204RNA EEC (PRP)
X204RNA EEC (PRP/HSR)
If configured as PRP device.
1. Both L power supplies are connected
(redundant supply).
2. One L power supply is connected
(non-redundant supply).
3. Power supply L1 and L2 are not connected or supply voltages are <14 V.
52
LED lit red
1, 2, 3, 4, 5
1, 3, 4, 5
1, 3, 4, 5
LED lit green
1
4
4
LED lit yellow
6
6
6
LED lit yellow
2
-
-
Operating Instructions, 04/2022, C79000-G8976-C342-07
LED not lit
7
7
7
LED not lit
3
5
5
SCALANCE X-200RNA