11.4 SIA – IFP-2000 Panel Dialer:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1. The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel
ID (PP), 2 digit Module Number (MM) and a 4 digit Event Parameter (ZZZZ).
2. Based on the actual Event Code, the Module Number or Event Parameter fields might not
contain pertinent information. In that case the field will contain zeros.
3. The account number is sent using an account block that is separate from the event block.
4. Multiple events can be sent within a single event block. Events are separated by a "/" char-
acter.
5. Event parameter can be a Zone, Point or Circuit Number.
6. "pi" modifier event is not used.
7. Panel can be set to report by either Point or Zone.